Review of IEC 62895 regarding Electrical Type Tests on extruded MVDC Cable Systems

Patrik Alexander Ratheiser*, Uwe Schichler

*Korrespondierende/r Autor/-in für diese Arbeit

Publikation: KonferenzbeitragPaperBegutachtung

Abstract

HVDC transmission is becoming an ever more important issue at present. Simultaneously, MVDC transmission will increase in the future. A commercial 12/20 kV AC XLPE cable has passed the electrical type test specified in IEC 62895 and the optimized PQ test for MVDC cable systems. Therefore, an MVAC cable system should be fully qualified for DC operation at ±55 kV. However, IEC 62895 gives recom¬mendations for high voltage tests, but without considering the technical differences between HVDC and MVDC cables. The type test in IEC 62895 is thus analysed and an optimized type test for the MVDC level is proposed.
Originalspracheenglisch
Seitenumfang6
PublikationsstatusVeröffentlicht - 9 Nov. 2021
VeranstaltungJicable HVDC'21 - International symposium on HVDC cable systems - BluePoint Liege, Liège, Belgien
Dauer: 8 Nov. 202110 Nov. 2021
https://www.hvdc21.jicable.org/

Konferenz

KonferenzJicable HVDC'21 - International symposium on HVDC cable systems
KurztitelJicable HVDC'21
Land/GebietBelgien
OrtLiège
Zeitraum8/11/2110/11/21
Internetadresse

Fingerprint

Untersuchen Sie die Forschungsthemen von „Review of IEC 62895 regarding Electrical Type Tests on extruded MVDC Cable Systems“. Zusammen bilden sie einen einzigartigen Fingerprint.