Strong and Weak Electric Fields Interfering: Capacitive Icing Detection and Capacitive Energy Harvesting on a 220 kV High-Voltage Overhead Power Line

Michael Johannes Moser, Thomas Bretterklieber, Hubert Zangl, Georg Brasseur

    Publikation: Beitrag in einer FachzeitschriftArtikelBegutachtung

    Abstract

    This paper focuses on problems which arise when both a power-harvesting system based on a capacitive principle and a capacitive measurement device [i.e., a capacitance-to-digital converter (CDC)] are used in one electronic system to build up an autonomous measurement device for icing detection on a high-voltage overhead power line. The overall capacitance of the measurement circuitry between the conductor and the energy harvester shell must remain within a well-defined range to keep the energy-harvesting circuitry operational and to operate the CDC within its specifications. A decoupling solution for both the data path and the power supply unit has been implemented and verified experimentally in a high-voltage laboratory and a field test.
    Originalspracheenglisch
    Seiten (von - bis)2597-2604
    FachzeitschriftIEEE Transactions on Industrial Electronics
    Jahrgang58
    Ausgabenummer7
    DOIs
    PublikationsstatusVeröffentlicht - 2011

    Fields of Expertise

    • Sonstiges

    Treatment code (Nähere Zuordnung)

    • Application
    • Experimental

    Fingerprint

    Untersuchen Sie die Forschungsthemen von „Strong and Weak Electric Fields Interfering: Capacitive Icing Detection and Capacitive Energy Harvesting on a 220 kV High-Voltage Overhead Power Line“. Zusammen bilden sie einen einzigartigen Fingerprint.